Enhanced Heat Sink Performance Utilizing Capillary-Driven Evaporation.
Mueller, Stuart.
2011
-
Abstract: Heat sinks
with the same form factor, but lower thermal resistance than currently available are
desirable in many applications. For example, they would benefit the electronics
packaging industry by accommodating increased heat dissipation in reduced form factors.
An enhanced longitudinally-finned heat sink that exploits evaporative cooling to
significantly reduce its thermal resistance ... read morewas modeled, fabricated and tested. A 1
mm-thick layer of (porous) sintered copper powder coated the entire (32 mm x 28 mm x 14
mm) heat sink and (porous) sintered copper powder legs were immersed in an underlying
water reservoir maintained at the temperature of the base of the heat sink. The assembly
was placed in a wind tunnel in the fully-shrouded configuration and (dry) nitrogen with
(upstream) velocities ranging from 1 m/s to 4 m/s flowed through the heat sink.
Capillary forces maintained a thin, evaporating film of water. Due to the high latent
heat of evaporation of water, large thermal resistance reductions are observed. The
thermal resistance of the coated heat sink was 3.4 to 4.7 times lower than that of an
uncoated heat sink of the same geometry. Both heat sinks were tested over a range of 0 W
to 20 W heat loads when (upstream) velocity equaled 2 m/s and over an (upstream)
velocity range from 1 m/s to 4 m/s when heat load was 15 W. The sintered heat sink was
tested with increasing power at 2 m/s until the heater burned out at 59 W. At this
heater input, the sintered heat sink reached 43oC above the ambient temperature. To
achieve the same temperature rise, the control heat sink required only 12 W of power,
almost five times less. External flow over a coated flat plate was also investigated and
similar reductions in thermal resistance
observed.
Thesis (M.S.)--Tufts University, 2011.
Submitted to the Dept. of Mechanical Engineering.
Advisor: Marc Hodes.
Committee: Alan Lyons, and Douglas Matson.
Keyword: Mechanical Engineering.read less - ID:
- pr76fg80t
- Component ID:
- tufts:20939
- To Cite:
- TARC Citation Guide EndNote